Drago DN28 Series 3-Way Isolation Amplifier, Fixed Ranges
Benefits of the DN28 Measurement Aplifiers with Galvanic Isolation
- Galvanic isolation of standard process signals.
- Various combinations of I/O ranges available.
- Compact, rugged, DIN-rail mountable modules.
Drago DN28 Series 3-Way Isolation Amplifier, Fixed Ranges
The 3-way isolation amplifier is used for electrical isolation and conversion of standard process signals. The signal combination is selected by the order no. The 3-way isolation guarantees reliable decoupling of the sensor circuit from the processing circuit and prevents linked measurement circuits from influencing each other. The protective separation with high isolation level provides protection for personnel and downstream devices against impermissibly high voltage.
- 3-way isolation amplifier.
- Input and output signal 0...20 mA, 4...20 mA oder 0...10 V (see table below).
- Test voltage 2.5 kV.
- Working voltage (basic insulation): Up to 600 VAC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits.
- Power supply 24 VAC/DC, AC 48...62 Hz, approx. 2 VA, DC approx. 0.7 W.
- Construction 11.2 mm housing, protection type: IP20.
- Connection 2.5 mm², AWG 14. Weight approx. 50 g.
Model Overview
Model | Code | Input | Output |
Range | Range | ||
DN28P- | 12 | 0...20 mA | 0...20 mA |
32 | 4...20 mA | 0...20 mA | |
52 | 0...10 V | 0...20 mA | |
14 | 0...20 mA | 4...20 mA | |
22 | 4...20 mA | 4...20 mA | |
54 | 0...10 V | 4...20 mA | |
16 | 0...20 mA | 0...10 V | |
36 | 4...20 mA | 0...10 V | |
56 | 0...10 V | 0...10 V |
Other combinations on request!
Included: Module, instructions for use.
Information on product safety:
Manufacturer:
DRAGO Automation GmbH, Waldstrasse 86-90, 13403 Berlin/DEU
www.drago-automation.de